GTB8LE-80:
GB/T16917.1
IEC61009-1
Polarity: 1P+N/2P
Function: Short circuit protection, overload protection, leakage protection (AC type), control
Rated frequency (f (Hz)): 50
Rated operating voltage (Ue (V)): AC230
Rated current (In (A)): 6,10,16,20,25,32,40,50,63
Rated insulation voltage (Ui (V)): 500
Rated impulse withstand voltage (Uimp (kV)): 4
Rated short-circuit breaking capacity (Icu (kA)): 3, 6
Rated residual operating current (I △ n (mA)): 30, 50, 100
Instantaneous release characteristics: C: 5In~10In, D: 10In~14In
Service life (O~C): Actual average electrical life: 4000, standard average electrical life: 4000, actual average mechanical life: 10000, standard average mechanical life: 10000
Connection and installation
Protection level: IP20
Wiring capacity (mm2): ≤ 25
Operating ambient temperature (℃): -5~+40
Moisture and heat resistance: Class 2
Altitude (m): ≤ 2000
Relative humidity of the air: not exceeding 95 at+20 ℃? At 40 ℃, not exceeding 50%
Pollution level: 2
Installation environment: a place without significant vibration and impact
Installation category: Level III
Installation method: DIN standard rail
Dimensions (mm): Width (W): 36 (MAX), Length (D): 81 (MAX), Height (H): 77.5 (MAX)