GTB6-63:
GB/T10963.1
IEC60898-1
Polarity: 1P/2P/3P/4P
Function: Short circuit protection, overload protection, isolation
Rated frequency (f (Hz)): 50
Rated operating voltage (Ue (V)): AC 230/400 (1P), AC 400 (2P, 3P, 4P)
Rated current (In (A)): 6,10,16,20,25,32,40,50,63
Rated insulation voltage (Ui (V)): 400
Rated impulse withstand voltage (Uimp (kV)): 4
Rated short-circuit breaking capacity (Icn (kA)): 6
Current limiting level: 3
Instantaneous release characteristics: C: 5In~10ln, D: 10ln~14In
Release type: thermal magnetic type
Service life: Actual average electrical life: 4000, standard average electrical life: 4000, actual average mechanical life: 10000, standard average electrical life: 10000
Connection and installation
Protection level: IP20
Wiring capacity (mm2): ≤ 25
Operating environment temperature: -5~+40
Moisture and heat resistance: Class 2
Altitude: ≤ 2000
Relative humidity of the air: not exceeding 95% at+20 ℃; +At 40 ℃, not exceeding 50%
Pollution level: 2
Installation environment: a place without significant vibration and impact
Installation category: Level III
Installation method: DIN standard rail
Dimensions (mm): Width (W): 18/36/54/72, Length (D): 80 (MAX)/80 (MAX)/80 (MAX)/80 (MAX), (H): 77.5 (MAX)/79 (MAX)/79 (MAX)/79 (MAX)
GTB6-125:
GB/T14048.2
IEC60947-2
Polarity: 1P/2P/3P/4P
Function: Short circuit protection, overload protection, isolation, control
Rated frequency (f (Hz)): 50
Rated operating voltage (Ue (V)): 230V~400V~
Rated current (In (A)): 63,80100125
Rated insulation voltage (Ui (V)): 500
Rated impulse withstand voltage (Uimp (kV)): 6
Rated short-circuit breaking capacity (Icn (kA)): Ics=7.5; Icu=10
Current limiting level: 3
Instantaneous release characteristic: 10ln ± 20%
Release type: thermal magnetic type
Service life: Actual average electrical life: 1500, standard average electrical life: 1500, actual average mechanical life: 8500, standard average electrical life: 8500
Connection and installation
Protection level: IP20
Wiring capacity (mm2): ≤ 50
Operating environment temperature: -5~+40
Moisture and heat resistance: Class 2
Altitude: ≤ 2000
Relative humidity of the air: not exceeding 95% at+20 ℃; +At 40 ℃, not exceeding 50%
Pollution level: 2
Installation environment: a place without significant vibration and impact
Installation category: Level III
Installation method: DIN standard rail
Dimensions (mm): Width (W): 27/54/81/108, Length (D): 84/84/84/84, (H): 73/78/78/78
GTB6LE-63:
GB/T16917.1
IEC61009-1
Polarity: 1P+N/2P/3P/3P+N/4P
Function: Short circuit protection, overload protection, leakage protection (AC type), control
Rated frequency (f (Hz)): 50
Rated operating voltage (Ue (V)): AC 230 (1P+N), AC 400 (3P, 3P+N, 4P)
Rated current (In (A)): 6,10,16,20,25,32,40,50,63
Rated insulation voltage (Ui (V)): 400
Rated impulse withstand voltage (Uimp (kV)): 4
Rated short-circuit breaking capacity (Icn (kA)): 6
Rated residual operating current (I △ n (mA)): 30
Instantaneous release characteristics: C: 5In~10ln, D: 10ln~14In
Service life: Actual average electrical life: 4000, standard average electrical life: 4000, actual average mechanical life: 10000, standard average electrical life: 10000
Connection and installation
Protection level: IP20
Wiring capacity (mm2): ≤ 25
Operating environment temperature: -5~+40
Moisture and heat resistance: Class 2
Altitude: ≤ 2000
Relative humidity of the air: not exceeding 95% at+20 ℃; +At 40 ℃, not exceeding 50%
Pollution level: 2
Installation environment: a place without significant vibration and impact
Installation category: Level II
Installation method: DIN standard rail
Dimensions (mm): Width (W): 54/72/103/117/135, Length (D): 97 (MAX)/97 (MAX)/97 (MAX)/97 (MAX)/97 (MAX), (H): 77.5 (MAX)/79 (MAX)/79 (MAX)/79 (MAX)/79 (MAX)
GTB6LE-125:
GB/T14048.2
IEC60947-2
Polarity: 1P+N/2P/3P/3P+N/4P
Function: Short circuit protection, overload protection, leakage protection, isolation, control
Rated frequency (f (Hz)): 50
Rated operating voltage (Ue (V)): 230V~/400V~
Rated current (In (A)): 63,80100125
Rated insulation voltage (Ui (V)): 500
Rated impulse withstand voltage (Uimp (kV)): 6
Rated short-circuit breaking capacity (Icn (kA)): 6
Current limiting level: 3
Instantaneous release characteristic: 10In ± 20%
Remaining tripping current type: AC
Service life: Actual average electrical life: 1500, standard average electrical life: 1500, actual average mechanical life: 8500, standard average electrical life: 8500
Connection and installation
Protection level: IP20
Wiring capacity (mm2): ≤ 50
Operating environment temperature: -5~+40
Moisture and heat resistance: Class 2
Altitude: ≤ 2000
Relative humidity of the air: not exceeding 95% at+20 ℃; +At 40 ℃, not exceeding 50%
Pollution level: 2
Installation environment: a place without significant vibration and impact
Installation category: Level III
Installation method: DIN standard rail
Dimensions (mm): Width (W): 54/81/108/108/135, Length (D): 113 (MAX)/113 (MAX)/113 (MAX)/113 (MAX)/113 (MAX), (H): 73/78/78/78