GTM6E-125:
GB/T14048.2
IEC60947-2
Shell level (Inm (A)): 125
Operating frequency (Hz): 50
Breaking type: L/M/H
Polarity: 3P4P/3P4P/3P4P
Rated current (In (A)): 12~32, 40~100, 50~125 adjustable
Rated insulation voltage (Ui (V)): 1000
Rated impulse withstand voltage (Uimp (kV)): 8
Rated operating voltage (Ue (V)): AV400/690
Flying arc distance (mm): ≯ 50
Rated ultimate short-circuit breaking capacity (Icu (kA)): 400V: 35/50/70690: 20:20/20
Rated operating short-circuit breaking capacity (Icu (kA)): 400V: 25/35/50690:10/10/10
Rated short-time withstand current (kA/1s): 1.5
Selective category: A
Service life: Mechanical life (times) Maintenance free: 20000/Mechanical life (times) Maintenance available: 40000/Electrical life (times): 8000
Dimensions (mm): Width (W) (3P/4P): 92/122/92/122/92/122, Length (L): 150, Height (H): 113
Installation board hole size (mm): Width (A) (3P/4P): 30/60/30/60/30/60, Length (B): 129, Diameter (φ): 5
Accessory selection
Alarm contact 08: □
Split release 10: □
Auxiliary contact 20: □
Undervoltage release 30: □
Two sets of auxiliary contacts 60: □
Directly rotate handle Z: □
Extended Rotating Handle Z (Extended): □
Electric operating mechanism P (CD2): □
Connection board: □
Rear wiring R: □
Plug in board wiring PR: □
Plug in board front wiring PF: □
Pull out formula:-
MODBUS communication module D: □
GTM6E-250
GB/T14048.2
IEC60947-2
Shell level (Inm (A)): 250
Operating frequency (Hz): 50
Breaking type: L/M/H
Polarity: 3P4P/3P4P/3P4P
Rated current (In (A)): 100~250 adjustable
Rated insulation voltage (Ui (V)): 100
Rated impulse withstand voltage (Uimp (kV)): 8
Rated operating voltage (Ue (V)): AV400/690
Flying arc distance (mm): ≯ 50
Rated ultimate short-circuit breaking capacity (Icu (kA)): 400V: 35/50/70690: 20:20/20
Rated operating short-circuit breaking capacity (Icu (kA)): 400V: 25/35/50690:10/10/10
Rated short-time withstand current (kA/1s): 3
Selective category: A
Service life: Mechanical life (times) Maintenance free: 20000/Mechanical life (times) Maintenance available: 40000/Electrical life (times): 8000
Dimensions (mm): Width (W) (3P/4P): 104/142/104/142/104/142, Length (L): 165, Height (H): 117
Installation board hole size (mm): Width (A) (3P/4P): 35/70/35/70/35/70, Length (B): 126, Diameter (φ): 5
Accessory selection
Alarm contact 08: □
Split release 10: □
Auxiliary contact 20: □
Undervoltage release 30: □
Two sets of auxiliary contacts 60: □
Directly rotate handle Z: □
Extended Rotating Handle Z (Extended): □
Electric operating mechanism P (CD2): □
Connection board: □
Rear wiring R: □
Plug in board wiring PR: □
Plug in board front wiring PF: □
Pull out formula:-
MODBUS communication module D: □
GTM6E-400:
GB/T14048.2
IEC60947-2
Shell level (Inm (A)): 400
Operating frequency (Hz): 50
Breaking type: L/M/H
Polarity: 3P4P/3P4P/3P4P
Rated current (In (A)): 160~400 adjustable
Rated insulation voltage (Ui (V)): 1000
Rated impulse withstand voltage (Uimp (kV)): 8
Rated operating voltage (Ue (V)): AV400/690
Flying arc distance (mm): ≯ 100
Rated ultimate short-circuit breaking capacity (Icu (kA)): 400V: 50/70/100690: 20:20/20
Rated operating short-circuit breaking capacity (Icu (kA)): 400V: 35/50/70690:15/15/15
Rated short-time withstand current (kA/1s): 5
Selective Category: B
Service life: Mechanical life (times) Maintenance free: 10000/Mechanical life (times) Maintenance available: 20000/Electrical life (times): 7500
Dimensions (mm): Width (W) (3P/4P): 150/198/150/198/150/198, Length (L): 257, Height (H): 150
Installation board hole size (mm): Width (A) (3P/4P): 44/94/44/94/44/94, Length (B): 194, Diameter (φ): 7
Accessory selection
Alarm contact 08: □
Split release 10: □
Auxiliary contact 20: □
Undervoltage release 30: □
Two sets of auxiliary contacts 60: □
Directly rotate handle Z: □
Extended Rotating Handle Z (Extended): □
Electric operating mechanism P (CD2): □
Connection board: □
Rear wiring R: □
Plug in board wiring PR: □
Plug in board front wiring PF: □
Extraction formula: □
MODBUS communication module D: □
GTM6E-630:
GB/T14048.2
IEC60947-2
Shell level (Inm (A)): 630
Operating frequency (Hz): 50
Breaking type: L/M/H
Polarity: 3P4P/3P4P/3P4P
Rated current (In (A)): 250~630 adjustable
Rated insulation voltage (Ui (V)): 1000
Rated impulse withstand voltage (Uimp (kV)): 8
Rated operating voltage (Ue (V)): AV400/690
Flying arc distance (mm): ≯ 100
Rated ultimate short-circuit breaking capacity (Icu (kA)): 400V: 50/70/100690: 20:20/20
Rated operating short-circuit breaking capacity (Icu (kA)): 400V: 35/50/70690:15/15/15
Rated short-time withstand current (kA/1s): 8
Selective Category: B
Service life: Mechanical life (times) Maintenance free: 10000/Mechanical life (times) Maintenance available: 20000/Electrical life (times): 7500
Dimensions (mm): Width (W) (3P/4P): 150/198/150/198/150/198, Length (L): 257, Height (H): 150
Installation board hole size (mm): Width (A) (3P/4P): 44/94/44/94/44/94, Length (B): 194, Diameter (φ): 7
Accessory selection
Alarm contact 08: □
Split release 10: □
Auxiliary contact 20: □
Undervoltage release 30: □
Two sets of auxiliary contacts 60: □
Directly rotate handle Z: □
Extended Rotating Handle Z (Extended): □
Electric operating mechanism P (CD2): □
Connection board: □
Rear wiring R: □
Plug in board wiring PR: □
Plug in board front wiring PF: □
Extraction formula: □
MODBUS communication module D: □
GTM6E-800:
GB/T14048.2
IEC60947-2
Shell level (Inm (A)): 800
Operating frequency (Hz): 50
Breaking type: L/M/H
Polarity: 3P4P/3P4P/3P4P
Rated current (In (A)): 250~630, 320~800 adjustable
Rated insulation voltage (Ui (V)): 1000
Rated impulse withstand voltage (Uimp (kV)): 8
Rated operating voltage (Ue (V)): AV400/690
Flying arc distance (mm): ≯ 100
Rated ultimate short-circuit breaking capacity (Icu (kA)): 400V: 50/70/100690: 20:20/20
Rated operating short-circuit breaking capacity (Icu (kA)): 400V: 35/50/70690:15/15/15
Rated short-time withstand current (kA/1s): 10
Selective Category: B
Service life: Mechanical life (times) Maintenance free: 10000/Mechanical life (times) Maintenance available: 20000/Electrical life (times): 7500
Dimensions (mm): Width (W) (3P/4P): 210/280/210/280/280, Length (L): 280, Height (H): 150
Installation board hole size (mm): Width (A) (3P/4P): 70/140/70/140/70/140, Length (B): 243, Diameter (φ): 7
Accessory selection
Alarm contact 08: □
Split release 10: □
Auxiliary contact 20: □
Undervoltage release 30: □
Two sets of auxiliary contacts 60: □
Directly rotate handle Z: □
Extended Rotating Handle Z (Extended): □
Electric operating mechanism P (CD2): □
Connection board: □
Rear wiring R: □
Plug in board wiring PR: □
Plug in board front wiring PF: □
Extraction formula: □
MODBUS communication module D: □