GTM6Z-400L:
Shell level rated current (Inm (A)): 400
Rated current (In (A)): 63,801001251460180200225250320350400
Rated insulation voltage (Ui (V)): 1600
Rated impulse withstand voltage (Uimp (kV)): 12
Polar number: 2P
Rated operating voltage (Ue (V)): DC 1500
Selective category: A
Rated ultimate short-circuit breaking capacity (Icu (kA)): 20
Rated operating short-circuit breaking capacity (Ics (kA)): 16
Single pole short-circuit breaking capacity 1P (IIT (kA)): 1.5
Electrical lifespan (times): 3000
Mechanical lifespan, maintenance free (times): 2000
Mechanical lifespan, with maintenance (times): 30000
Dimensions (mm): L: 200/W: 80/H: 115
Flying arc distance (mm): zero
Wiring method: Front board wiring (both up and down incoming wires are acceptable)
GTM6Z-400M:
Shell level rated current (Inm (A)): 400
Rated current (In (A)): 63,801001251460180200225250320350400
Rated insulation voltage (Ui (V)): 1600
Rated impulse withstand voltage (Uimp (kV)): 12
Polar number: 2P
Rated operating voltage (Ue (V)): DC 1500
Selective category: A
Rated ultimate short-circuit breaking capacity (Icu (kA)): 50
Rated operating short-circuit breaking capacity (Ics (kA)): 20
Single pole short-circuit breaking capacity 1P (IIT (kA)): 2.5
Electrical lifespan (times): 3000
Mechanical lifespan, maintenance free (times): 2000
Mechanical lifespan, with maintenance (times): 30000
Dimensions (mm): L: 200/W: 80/H: 115
Flying arc distance (mm): zero
Wiring method: Front board wiring (both up and down incoming wires are acceptable)
GTM6Z-630L:
Shell level rated current (Inm (A)): 630
Rated current (In (A)): 25030035040045050500550630
Rated insulation voltage (Ui (V)): 1600
Rated impulse withstand voltage (Uimp (kV)): 12
Polar number: 2P
Rated operating voltage (Ue (V)): DC 1500
Selective category: A
Rated ultimate short-circuit breaking capacity (Icu (kA)): 20
Rated operating short-circuit breaking capacity (Ics (kA)): 16
Single pole short-circuit breaking capacity 1P (IIT (kA)): 2.5
Electrical lifespan (times): 1500
Mechanical lifespan, maintenance free (times): 15000
Mechanical lifespan, with maintenance (times): 30000
Dimensions (mm): Length L: 256/Width W: 98/Height H: 135
Flying arc distance (mm): zero
Wiring method: Front board wiring (both up and down incoming wires are acceptable)
GTM6Z-630M:
Shell level rated current (Inm (A)): 630
Rated current (In (A)): 25030035040045050500550630
Rated insulation voltage (Ui (V)): 1600
Rated impulse withstand voltage (Uimp (kV)): 12
Polar number: 2P
Rated operating voltage (Ue (V)): DC 1500
Selective category: A
Rated ultimate short-circuit breaking capacity (Icu (kA)): 50
Rated operating short-circuit breaking capacity (Ics (kA)): 20
Single pole short-circuit breaking capacity 1P (IIT (kA)): 5
Electrical lifespan (times): 1500
Mechanical lifespan, maintenance free (times): 15000
Mechanical lifespan, with maintenance (times): 30000
Dimensions (mm): Length L: 256/Width W: 98/Height H: 135
Flying arc distance (mm): zero